What is the Belimo EV200H Energy Valve?
EV200H joins a two-way control valve with an ultrasonic flow meter. It also reads supply and return temperature and uses Belimo's energy-control logic. The listed setup works with water or up to 60% glycol. It supports several building-control links. Its 100 gpm nominal flow is a ceiling, not a steady target. Check valve authority and meter accuracy through the full rack-loop load range. For direct-to-chip use, Belimo directs customers to its data-center team. The design should set fail-safe action, pressure range and sensor location. It should also define glycol correction, saved data, cloud policy and behavior after a network loss. One setup may not fit a server branch, rack, coolant distribution unit (CDU) and plant coil. Each point has a different flow range and failure risk. The controls submittal should name each command and update rate. It should give alarm limits, fallback values and cloud status. Start-up tests should compare shown flow and heat transfer with calibrated tools and the real fluid. Cover firmware support, password custody and spare-sensor calibration. A cyber review is needed. Staff must know how to recover local logs after a controller fault.