What is the Veolia TrueSense Ready-Set-Go?
TrueSense Ready-Set-Go, or RSG, is a Veolia cooling-water controller. It measures pH, oxidation-reduction potential, and conductivity. Supported programs can also track chemical levels in real time. In an Illinois data-center case, an RSG measured pH and controlled sulfuric acid feed. Remote checks and alarms were also used. Veolia says the full treatment change doubled tower cycles and cut water demand. The source does not name the site. It omits the controller build, sensors, setpoints, raw trends, and an outside audit. Acid feed needs secondary containment and compatible pumps and tubing. It also needs interlocks, air flow, protective gear, and steps for failed sensors or pumps. Each reading needs an approved range, accuracy, calibration method, and replacement interval. Sample conditioning, outputs, links, local logic, and fail positions also require review. Alarm routes, network-loss behavior, data retention, access control, remote support, proof of feed, and manual operation must be clear. Available material gives no full hardware specification, cyber certificate, or guaranteed savings. The submittal must separate measured data from calculated or entered values. It must also show which outputs can start chemical feed or blowdown. Tests should cover dirty or failed probes, lost sample flow, stuck feed equipment, empty tanks, network loss, delayed alarms, and power return. Calibration standards, spare probes, backups, user roles, raw trends, local fallback, and the remote-service response time must be stated.