Coolant distribution unit Product

Carrier CDU 65LL

A coolant distribution unit rated at 1,350 kW with a 4°C approach, offered with a heat exchanger that narrows the approach to 2°C.

CDU1.35 MW2°C approachQuantumLeap

Direct answer

What this record says

Carrier CDU 65LL is a cooling product from Carrier. The supplier publishes a capacity of 1,350 kW at 4°C approach, not yet reviewed as a normalized claim. Its lifecycle status is available. Last reviewed Sept. 4, 2026 against 2 sources.

2 sourcesReviewed Sept. 4, 2026
Manufacturer
Carrier
Rated capacity
1,350 kW at 4°C approachNo duty point stated
Total flow
0 to 1,650 liters per minute at 350 kPa, single pump
Status
Available

Product brief

What the record shows

Carrier's entry into liquid cooling is a liquid-to-liquid coolant distribution unit sold under its QuantumLeap data center range. The published rating is 1,350 kW at a 4 degree Celsius approach temperature difference, with flow from zero to 1,650 liters per minute at 350 kPa using a single pump. Carrier says the optional high-efficiency heat exchanger brings the approach down to 2 degrees against an industry-common 4.

A narrower approach means the server loop runs closer to facility water, so the chiller can be asked for warmer water, and Carrier claims up to 15 percent chiller energy saving on that basis. Treat the saving as a modelled figure: it depends on the plant, the climate and the control strategy, none of which the flyer states. Availability features include dual pumps in N+1, sensor redundancy and an in-unit uninterruptible power supply.

The cabinet is 986 mm deep with access on three sides, and controls speak BACnet, Modbus and Carrier's own protocol. The family extends to 5 MW in skid designs. Carrier does not publish the secondary fluid, the pressure drop across the exchanger, or the electrical load.

Ask for the selection at the site's own facility-water temperature, and for the assumptions behind the 15 percent figure before it is used in a business case.

Capacity figures are supplier-reported unless the source says otherwise. Compare products at the same temperatures, flow, pressure, and redundancy state.

SpecificationSupplier-stated
Protocols
BACnet, Modbus, CCNSupplier wording, not yet normalized
Redundancy
Dual pumps N+1, sensor redundancy, in-unit UPSSupplier wording, not yet normalized
Coolant flow
0 to 1,650 liters per minute at 350 kPa, single pumpSupplier wording, not yet normalized
Cabinet depth
986 mm, three-sided accessSupplier wording, not yet normalized
Rated capacity
1,350 kW at 4°C approachSupplier wording, not yet normalized
Approach temperature
4°C, or 2°C with the high-efficiency exchangerSupplier wording, not yet normalized
Maximum configured capacity
Up to 5 MW in skid designsSupplier wording, not yet normalized
Manufacturer
Carrier

Connected records

Compatible architecture

Connected records

Equipment category

Evidence ledger

Sources and evidence

The links below show where the factual claims came from. Supplier specifications remain supplier-reported unless the record names independent operating evidence.

  1. 01
  2. 02
Record information
Record ID
DCC / PROD / CARRIER-CDU-
Record reviewed
Sept. 4, 2026
Record first published
Sept. 4, 2026
External sources
2
Search visibility
Offered to search engines

Required fields this record has not addressed yet, most important first:

  • Rating conditions
  • Facility-water supply and return
  • Public deployment evidence
  • Pressure or head
  • Dimensions
  • Deployment format

Decide between

Comparable products

The same equipment category from other manufacturers, most-evidenced first.

View all products

Add two or more, then open the comparison to see every stated claim, its duty point, and its source side by side.

Direct answers

Frequently asked questions

Direct answers drawn from the record, its comparison fields, and the evidence linked below.

What is the Carrier CDU 65LL?

Carrier's entry into liquid cooling is a liquid-to-liquid coolant distribution unit sold under its QuantumLeap data center range. The published rating is 1,350 kW at a 4 degree Celsius approach temperature difference, with flow from zero to 1,650 liters per minute at 350 kPa using a single pump. Carrier says the optional high-efficiency heat exchanger brings the approach down to 2 degrees against an industry-common 4. A narrower approach means the server loop runs closer to facility water, so the chiller can be asked for warmer water, and Carrier claims up to 15 percent chiller energy saving on that basis. Treat the saving as a modelled figure: it depends on the plant, the climate and the control strategy, none of which the flyer states. Availability features include dual pumps in N+1, sensor redundancy and an in-unit uninterruptible power supply. The cabinet is 986 mm deep with access on three sides, and controls speak BACnet, Modbus and Carrier's own protocol. The family extends to 5 MW in skid designs. Carrier does not publish the secondary fluid, the pressure drop across the exchanger, or the electrical load. Ask for the selection at the site's own facility-water temperature, and for the assumptions behind the 15 percent figure before it is used in a business case.

Who makes the Carrier CDU 65LL?

Carrier makes it. We file it under coolant distribution units, and its status is available.

What are the key specifications for the Carrier CDU 65LL?

Protocols: BACnet, Modbus, CCN; Redundancy: Dual pumps N+1, sensor redundancy, in-unit UPS; Coolant flow: 0 to 1,650 liters per minute at 350 kPa, single pump. These figures come from the supplier. Before comparing two products, restate both at your own water temperatures, flow, pressure, and redundancy, because a rating measured under favorable conditions will not hold on site.