Negative-pressure coolant distribution unit Product

Chilldyne CF-CDU300

A coolant distribution unit that holds the server loop below atmospheric pressure, rated at 300 kW with a 7°C approach.

negative pressure300 kWleak containmentwarm water

Direct answer

What this record says

Chilldyne CF-CDU300 is a cooling product from Chilldyne. The supplier publishes a capacity of 300 kW at 7°C approach, not yet reviewed as a normalized claim. Its lifecycle status is available. Last reviewed Sept. 4, 2026 against 2 sources.

2 sourcesReviewed Sept. 4, 2026
Manufacturer
Chilldyne
Rated capacity
300 kW at 7°C approachNo duty point stated
Total flow
Up to 300 liters per minute
Status
Available

Product brief

What the record shows

Most coolant distribution units push fluid into the server loop. The CF-CDU300 pulls it instead, holding the loop under vacuum so a failed seal draws air inward rather than pushing coolant onto hardware. Chilldyne rates the unit at 300 kW with a 7 degree Celsius approach to facility water, and states a 2 degree approach when the load falls to 200 kW.

Maximum secondary flow is 300 liters per minute. Facility water may arrive between 2 and 45 degrees Celsius and leave as warm as 60 degrees, which allows a cooling tower rather than a chiller in many climates. The loop runs at a maximum of 22 inches of mercury of vacuum, driven by a 3 horsepower liquid ring pump, and the primary side requires 100 micron filtration.

The cabinet measures 24 by 80 by 45 inches. Capacity here is a function of flow and temperature rise rather than a fixed number, and Chilldyne says so plainly: the same unit reaches a higher figure with colder water and a wider rise, and a lower one with warm water and a narrow rise. Ask for a selection at the site's own water temperature and permitted rise, the behaviour of the vacuum loop during a power interruption, and the cold-plate range approved for the intended processors.

Daikin Applied acquired Chilldyne in November 2025, so confirm which entity signs the warranty.

Capacity figures are supplier-reported unless the source says otherwise. Compare products at the same temperatures, flow, pressure, and redundancy state.

SpecificationSupplier-stated
Pump
3 hp liquid ringSupplier wording, not yet normalized
Footprint
24 × 80 × 45 inSupplier wording, not yet normalized
Coolant flow
Up to 300 liters per minuteSupplier wording, not yet normalized
Loop pressure
Maximum 22 inHg of vacuumSupplier wording, not yet normalized
Rated capacity
300 kW at 7°C approachSupplier wording, not yet normalized
Secondary fluid
Water or water-glycolSupplier wording, not yet normalized
Approach temperature
7°C at 300 kW, 2°C at 200 kWSupplier wording, not yet normalized
Primary supply temperature
2°C to 45°CSupplier wording, not yet normalized
Manufacturer
Chilldyne

Connected records

Compatible architecture

Connected records

Equipment category

Evidence ledger

Sources and evidence

The links below show where the factual claims came from. Supplier specifications remain supplier-reported unless the record names independent operating evidence.

  1. 01
  2. 02
Record information
Record ID
DCC / PROD / CHILLDYNE-CF
Record reviewed
Sept. 4, 2026
Newest source published
Nov. 5, 2025
Record first published
Sept. 4, 2026
External sources
2
Search visibility
Offered to search engines

Required fields this record has not addressed yet, most important first:

  • Rating conditions
  • Facility-water supply and return
  • Public deployment evidence
  • Redundancy
  • Deployment format

Decide between

Comparable products

The same equipment category from other manufacturers, most-evidenced first.

View all products

Add two or more, then open the comparison to see every stated claim, its duty point, and its source side by side.

Direct answers

Frequently asked questions

Direct answers drawn from the record, its comparison fields, and the evidence linked below.

What is the Chilldyne CF-CDU300?

Most coolant distribution units push fluid into the server loop. The CF-CDU300 pulls it instead, holding the loop under vacuum so a failed seal draws air inward rather than pushing coolant onto hardware. Chilldyne rates the unit at 300 kW with a 7 degree Celsius approach to facility water, and states a 2 degree approach when the load falls to 200 kW. Maximum secondary flow is 300 liters per minute. Facility water may arrive between 2 and 45 degrees Celsius and leave as warm as 60 degrees, which allows a cooling tower rather than a chiller in many climates. The loop runs at a maximum of 22 inches of mercury of vacuum, driven by a 3 horsepower liquid ring pump, and the primary side requires 100 micron filtration. The cabinet measures 24 by 80 by 45 inches. Capacity here is a function of flow and temperature rise rather than a fixed number, and Chilldyne says so plainly: the same unit reaches a higher figure with colder water and a wider rise, and a lower one with warm water and a narrow rise. Ask for a selection at the site's own water temperature and permitted rise, the behaviour of the vacuum loop during a power interruption, and the cold-plate range approved for the intended processors. Daikin Applied acquired Chilldyne in November 2025, so confirm which entity signs the warranty.

Who makes the Chilldyne CF-CDU300?

Chilldyne makes it. We file it under coolant distribution units, and its status is available.

What are the key specifications for the Chilldyne CF-CDU300?

Pump: 3 hp liquid ring; Footprint: 24 × 80 × 45 in; Coolant flow: Up to 300 liters per minute. These figures come from the supplier. Before comparing two products, restate both at your own water temperatures, flow, pressure, and redundancy, because a rating measured under favorable conditions will not hold on site.