Two-phase cooling system Product

Accelsius NeuCool IR80

An in-rack two-phase direct-to-chip cooling system demonstrated in co-innovation and high-density data-center environments.

two phasedirect-to-chipdielectricin rack

Direct answer

What this record says

Accelsius NeuCool IR80 is a cooling product from Accelsius. It is rated at 80 kW, with no duty point stated alongside the figure. Its lifecycle status is available. Last reviewed Aug. 9, 2026 against 2 sources.

2 sourcesReviewed Aug. 9, 2026
Manufacturer
Accelsius
Rated capacity
80 kWNo duty point stated
Total flow
Not recorded
Status
Available

Product brief

What the record shows

NeuCool IR80 is an in-rack, two-phase direct-to-chip system for cooling central processing units and graphics processing units. A low-pressure dielectric refrigerant boils in processor-mounted “vaporator” plates, then returns to the in-rack unit to condense and circulate again. Accelsius rates direct liquid cooling at 80 kW or more per rack and total rack cooling at 100 kW; its sheet says the plates target all processor heat, estimated as 75–80% of server heat.

The remaining load still needs air cooling. It also reports support above 4,500 W per socket, less than 1 kW of system power, N+1 power and pump redundancy, leak sensing, and several monitoring interfaces. These are vendor ratings, and the cited Equinix Ashburn installation is a co-innovation deployment rather than proof of fleet-wide production results.

Compatibility is not generic. Ask for the exact plate, internal plumbing, firmware, and warranty approval for every server configuration, even where a processor family appears on the vendor list. Confirm rack width and depth, seven-rack-unit space, power voltage, heat-rejection interface, ambient air allowance, refrigerant service process, and data-center-infrastructure-management integration.

Compare the quoted 80 kW at the project's facility-water temperature and failure state. The public sheet does not provide a full pump curve, refrigerant charge pressure, sound level, or field availability data. It also does not remove the need to plan condenser-side heat rejection and residual room cooling.

Capacity figures are supplier-reported unless the source says otherwise. Compare products at the same temperatures, flow, pressure, and redundancy state.

Specification7 reviewed claims
Rated capacity
80 kWRated direct cooling: “80 kW+ per rackSupplier reported · Accelsius · reviewed 2026-09-04
Parasitic power
1 kWReported system power: “Below 1 kWSupplier reported · Accelsius · reviewed 2026-09-04
Secondary fluid
Non-conductive dielectricSupplier reported · Accelsius · reviewed 2026-09-04
Format
In-rackSupplier reported · Accelsius · reviewed 2026-09-04
Cooling architecture
Two-phase direct-to-chipSupplier reported · Accelsius · reviewed 2026-09-04
Reference deployment
Equinix Ashburn CIFSupplier reported · Accelsius · reviewed 2026-09-04
Lifecycle
AvailableSupplier reported · Accelsius · reviewed 2026-09-04
Manufacturer
Accelsius

Connected records

Compatible architecture

Connected records

Equipment category

Evidence ledger

Sources and evidence

The links below show where the factual claims came from. Supplier specifications remain supplier-reported unless the record names independent operating evidence.

  1. 01
  2. 02
Record information
Record ID
DCC / PROD / ACCELSIUS-NE
Record reviewed
Aug. 9, 2026
Latest claim reviewed
Sept. 4, 2026
Newest source published
July 15, 2025
Record first published
Aug. 9, 2026
External sources
2
Search visibility
Offered to search engines

Required fields this record has not addressed yet, most important first:

  • Rating conditions
  • Total coolant flow
  • Facility-water supply and return
  • Technology-water temperature
  • Pressure or head
  • Redundancy
  • Dimensions

Decide between

Comparable products

The same equipment category from other manufacturers, most-evidenced first.

View all products

Add two or more, then open the comparison to see every stated claim, its duty point, and its source side by side.

Latest coverage

Intelligence mentioning Accelsius NeuCool IR80

View all intelligence mentioning accelsius neucool ir80

Direct answers

Frequently asked questions

Direct answers drawn from the record, its comparison fields, and the evidence linked below.

What is the Accelsius NeuCool IR80?

NeuCool IR80 is an in-rack, two-phase direct-to-chip system for cooling central processing units and graphics processing units. A low-pressure dielectric refrigerant boils in processor-mounted “vaporator” plates, then returns to the in-rack unit to condense and circulate again. Accelsius rates direct liquid cooling at 80 kW or more per rack and total rack cooling at 100 kW; its sheet says the plates target all processor heat, estimated as 75–80% of server heat. The remaining load still needs air cooling. It also reports support above 4,500 W per socket, less than 1 kW of system power, N+1 power and pump redundancy, leak sensing, and several monitoring interfaces. These are vendor ratings, and the cited Equinix Ashburn installation is a co-innovation deployment rather than proof of fleet-wide production results. Compatibility is not generic. Ask for the exact plate, internal plumbing, firmware, and warranty approval for every server configuration, even where a processor family appears on the vendor list. Confirm rack width and depth, seven-rack-unit space, power voltage, heat-rejection interface, ambient air allowance, refrigerant service process, and data-center-infrastructure-management integration. Compare the quoted 80 kW at the project's facility-water temperature and failure state. The public sheet does not provide a full pump curve, refrigerant charge pressure, sound level, or field availability data. It also does not remove the need to plan condenser-side heat rejection and residual room cooling.

Who makes the Accelsius NeuCool IR80?

Accelsius makes it. We file it under coolant distribution units, and its status is available.

What are the key specifications for the Accelsius NeuCool IR80?

Fluid: Non-conductive dielectric; Format: In-rack; Architecture: Two-phase direct-to-chip. These figures come from the supplier. Before comparing two products, restate both at your own water temperatures, flow, pressure, and redundancy, because a rating measured under favorable conditions will not hold on site.