Coolant distribution unit Product

Boyd ROL4000

An in-row coolant distribution unit rated at 2 MW with a 3°C approach, built to the fifth-generation Project Deschutes shape.

CDU2 MWProject Deschutesin row

Direct answer

What this record says

Boyd ROL4000 is a cooling product from Boyd. The supplier publishes a capacity of 2 MW at 3°C approach, not yet reviewed as a normalized claim. Its lifecycle status is available. Last reviewed Sept. 4, 2026 against 1 source.

1 sourceReviewed Sept. 4, 2026
Manufacturer
Boyd
Rated capacity
2 MW at 3°C approachNo duty point stated
Total flow
1,890 liters per minute (500 gallons per minute)
Status
Available

Product brief

What the record shows

The ROL4000 is a liquid-to-liquid coolant distribution unit for a row of high-density racks. Boyd describes it as inspired by the fifth generation of Google's Project Deschutes design, which matters commercially: an operator standardising on that open specification can treat suppliers as interchangeable rather than bespoke. Boyd rates the unit at 2 megawatts with a 3 degree Celsius approach to facility water, which is a narrow approach and therefore implies a large heat exchanger for the duty.

Flow reaches 1,890 liters per minute, quoted as 500 gallons per minute, and the unit supplies up to 80 psi of available pressure to drive manifolds, control valves and cold plates. Availability features are stated rather than optional: seal-less N+1 pumps, a fully redundant power feed for each pump circuit, and 0.2 micron side-stream filtration. The cabinet is 1,651 by 1,199 by 2,364 mm.

Boyd does not publish the electrical load, the pressure drop on the primary side, the secondary fluid the rating assumes, or the minimum stable load, and the last of those matters for a hall that fills gradually. Ask for a selection at the site's facility-water temperature, the pump curve behind the 80 psi figure, and the capacity that remains with one pump out of service.

Capacity figures are supplier-reported unless the source says otherwise. Compare products at the same temperatures, flow, pressure, and redundancy state.

SpecificationSupplier-stated
Pumps
Seal-less, N+1, redundant power feed per circuitSupplier wording, not yet normalized
Footprint
1,651 × 1,199 × 2,364 mmSupplier wording, not yet normalized
Filtration
0.2 micron side streamSupplier wording, not yet normalized
Coolant flow
1,890 liters per minute (500 gallons per minute)Supplier wording, not yet normalized
Rated capacity
2 MW at 3°C approachSupplier wording, not yet normalized
Available pressure
Up to 80 psiSupplier wording, not yet normalized
Approach temperature
3°CSupplier wording, not yet normalized
Manufacturer
Boyd

Connected records

Compatible architecture

Connected records

Equipment category

Evidence ledger

Sources and evidence

The links below show where the factual claims came from. Supplier specifications remain supplier-reported unless the record names independent operating evidence.

  1. 01
Record information
Record ID
DCC / PROD / BOYD-ROL4000
Record reviewed
Sept. 4, 2026
Newest source published
Oct. 29, 2025
Record first published
Sept. 4, 2026
External sources
1
Search visibility
Offered to search engines

Required fields this record has not addressed yet, most important first:

  • Rating conditions
  • Facility-water supply and return
  • Public deployment evidence
  • Deployment format

Decide between

Comparable products

The same equipment category from other manufacturers, most-evidenced first.

View all products

Add two or more, then open the comparison to see every stated claim, its duty point, and its source side by side.

Direct answers

Frequently asked questions

Direct answers drawn from the record, its comparison fields, and the evidence linked below.

What is the Boyd ROL4000?

The ROL4000 is a liquid-to-liquid coolant distribution unit for a row of high-density racks. Boyd describes it as inspired by the fifth generation of Google's Project Deschutes design, which matters commercially: an operator standardising on that open specification can treat suppliers as interchangeable rather than bespoke. Boyd rates the unit at 2 megawatts with a 3 degree Celsius approach to facility water, which is a narrow approach and therefore implies a large heat exchanger for the duty. Flow reaches 1,890 liters per minute, quoted as 500 gallons per minute, and the unit supplies up to 80 psi of available pressure to drive manifolds, control valves and cold plates. Availability features are stated rather than optional: seal-less N+1 pumps, a fully redundant power feed for each pump circuit, and 0.2 micron side-stream filtration. The cabinet is 1,651 by 1,199 by 2,364 mm. Boyd does not publish the electrical load, the pressure drop on the primary side, the secondary fluid the rating assumes, or the minimum stable load, and the last of those matters for a hall that fills gradually. Ask for a selection at the site's facility-water temperature, the pump curve behind the 80 psi figure, and the capacity that remains with one pump out of service.

Who makes the Boyd ROL4000?

Boyd makes it. We file it under coolant distribution units, and its status is available.

What are the key specifications for the Boyd ROL4000?

Pumps: Seal-less, N+1, redundant power feed per circuit; Footprint: 1,651 × 1,199 × 2,364 mm; Filtration: 0.2 micron side stream. These figures come from the supplier. Before comparing two products, restate both at your own water temperatures, flow, pressure, and redundancy, because a rating measured under favorable conditions will not hold on site.