Coolant distribution unit Product

LITE-ON CL-LL-WCDU-6011

A coolant distribution unit rated at 600 kW with a 4°C approach at 600 liters per minute, in a 900 mm cabinet.

CDU600 kWdew point controlonline service

Direct answer

What this record says

LITE-ON CL-LL-WCDU-6011 is a cooling product from LITE-ON. The supplier publishes a capacity of 600 kW at 600 liters per minute, 4°C approach, not yet reviewed as a normalized claim. Its lifecycle status is available. Last reviewed Sept. 4, 2026 against 1 source.

1 sourceReviewed Sept. 4, 2026
Manufacturer
LITE-ON
Rated capacity
600 kW at 600 liters per minute, 4°C approachNo duty point stated
Total flow
600 liters per minute at 2.45 bar external differential
Status
Available

Product brief

What the record shows

LITE-ON publishes this coolant distribution unit with the full duty point attached, which is rarer than it should be. The rating is 600 kW at 600 liters per minute with a 4 degree Celsius approach temperature difference. Nominal flow is quoted as 600 liters per minute against 2.45 bar of external differential pressure, so the pump curve and the piping loss are both accounted for.

The primary loop accepts water from 7 to 35 degrees Celsius; the secondary loop runs between 15 and 45 degrees and holds 61 liters. Coolant is treated water or 25 percent propylene glycol. The cabinet measures 2,038 by 900 by 1,200 mm and weighs 660 kg.

Pumps are dual redundant and serviceable online, as are the integrated 25 micron filters. Power draw is 6 kW, from either a 190 to 220 volt or a 380 to 480 volt three-phase supply, and models with an automatic transfer switch are available. Noise is stated below 58 decibels at three meters.

Dew point control is included, which matters when the secondary loop can run below room dew point. Pipe connections are ISO 7241-B stainless steel flanges. LITE-ON does not state the primary flow rate or the capacity with one pump out of service.

Ask for both, and for the selection at the site's own primary water temperature.

Capacity figures are supplier-reported unless the source says otherwise. Compare products at the same temperatures, flow, pressure, and redundancy state.

SpecificationSupplier-stated
Noise
Below 58 dBA at 3 mSupplier wording, not yet normalized
Weight
660 kgSupplier wording, not yet normalized
Footprint
900 × 1,200 mm, 2,038 mm tallSupplier wording, not yet normalized
Coolant flow
600 liters per minute at 2.45 bar external differentialSupplier wording, not yet normalized
Rated capacity
600 kW at 600 liters per minute, 4°C approachSupplier wording, not yet normalized
Secondary fluid
Treated water or 25% propylene glycolSupplier wording, not yet normalized
Power consumption
6 kWSupplier wording, not yet normalized
Approach temperature
4°CSupplier wording, not yet normalized
Primary loop temperature
7°C to 35°CSupplier wording, not yet normalized
Secondary loop temperature
15°C to 45°CSupplier wording, not yet normalized
Manufacturer
LITEON Technology

Connected records

Compatible architecture

Connected records

Equipment category

Evidence ledger

Sources and evidence

The links below show where the factual claims came from. Supplier specifications remain supplier-reported unless the record names independent operating evidence.

  1. 01
Record information
Record ID
DCC / PROD / LITEON-WCDU-
Record reviewed
Sept. 4, 2026
Record first published
Sept. 4, 2026
External sources
1
Search visibility
Offered to search engines

Required fields this record has not addressed yet, most important first:

  • Rating conditions
  • Facility-water supply and return
  • Public deployment evidence
  • Pressure or head
  • Redundancy
  • Deployment format

Decide between

Comparable products

The same equipment category from other manufacturers, most-evidenced first.

View all products

Add two or more, then open the comparison to see every stated claim, its duty point, and its source side by side.

Direct answers

Frequently asked questions

Direct answers drawn from the record, its comparison fields, and the evidence linked below.

What is the LITE-ON CL-LL-WCDU-6011?

LITE-ON publishes this coolant distribution unit with the full duty point attached, which is rarer than it should be. The rating is 600 kW at 600 liters per minute with a 4 degree Celsius approach temperature difference. Nominal flow is quoted as 600 liters per minute against 2.45 bar of external differential pressure, so the pump curve and the piping loss are both accounted for. The primary loop accepts water from 7 to 35 degrees Celsius; the secondary loop runs between 15 and 45 degrees and holds 61 liters. Coolant is treated water or 25 percent propylene glycol. The cabinet measures 2,038 by 900 by 1,200 mm and weighs 660 kg. Pumps are dual redundant and serviceable online, as are the integrated 25 micron filters. Power draw is 6 kW, from either a 190 to 220 volt or a 380 to 480 volt three-phase supply, and models with an automatic transfer switch are available. Noise is stated below 58 decibels at three meters. Dew point control is included, which matters when the secondary loop can run below room dew point. Pipe connections are ISO 7241-B stainless steel flanges. LITE-ON does not state the primary flow rate or the capacity with one pump out of service. Ask for both, and for the selection at the site's own primary water temperature.

Who makes the LITE-ON CL-LL-WCDU-6011?

LITE-ON makes it. We file it under coolant distribution units, and its status is available.

What are the key specifications for the LITE-ON CL-LL-WCDU-6011?

Noise: Below 58 dBA at 3 m; Weight: 660 kg; Footprint: 900 × 1,200 mm, 2,038 mm tall. These figures come from the supplier. Before comparing two products, restate both at your own water temperatures, flow, pressure, and redundancy, because a rating measured under favorable conditions will not hold on site.