Coolant distribution unit Product

Supermicro In-Rack CDU

A 4U in-rack coolant distribution unit rated to 250 kW on water as warm as 45°C, part of the DLC-2 stack.

CDU250 kWin rackwarm water

Direct answer

What this record says

Supermicro In-Rack CDU is a cooling product from Supermicro. The supplier publishes a capacity of Up to 250 kW, not yet reviewed as a normalized claim. Its lifecycle status is available. Last reviewed Sept. 4, 2026 against 2 sources.

2 sourcesReviewed Sept. 4, 2026
Manufacturer
Supermicro
Rated capacity
Up to 250 kWNo duty point stated
Total flow
Not recorded
Status
Available

Product brief

What the record shows

Supermicro's in-rack coolant distribution unit puts the heat exchanger inside the rack it serves, which shortens the loop and lowers the pressure the pumps must overcome. It occupies 4U and is rated to 250 kW, enough for one dense rack. Supermicro states operation on water up to 45 degrees Celsius, which removes the mechanical chiller from the critical path, and pairs that with a claim of up to 98 percent heat capture per rack when the whole DLC-2 stack is used.

The remaining few percent still leaves through air, so the room cannot be treated as thermally neutral. Two variants are listed: an EIA model with 2N redundant pumps drawing up to 1.2 kW, and an OCP model with N+1 pumps drawing up to 3 kW. Dimensions are 480 by 810 by 177 mm and 480 by 858 by 177 mm respectively, at 100 and 114 kg dry.

Power supplies are redundant. Management runs over Redfish, SNMP, a web interface and Supermicro's own orchestration software. An in-row unit at 1.8 MW is also offered for multi-rack pods.

Supermicro does not publish the approach temperature, the flow rate, the secondary fluid, or the pressure drop, so the 250 kW figure cannot be compared directly with a rival quoted at a named approach.

Capacity figures are supplier-reported unless the source says otherwise. Compare products at the same temperatures, flow, pressure, and redundancy state.

SpecificationSupplier-stated
Weight
100 kg or 114 kg without coolantSupplier wording, not yet normalized
Footprint
480 × 810 mm or 480 × 858 mm, 4U highSupplier wording, not yet normalized
Protocols
Redfish, SNMP, web interfaceSupplier wording, not yet normalized
Redundancy
2N pumps (EIA model) or N+1 pumps (OCP model)Supplier wording, not yet normalized
Rated capacity
Up to 250 kWSupplier wording, not yet normalized
Power consumption
Up to 1.2 kW or 3 kW by modelSupplier wording, not yet normalized
Supply temperature
Warm water up to 45°CSupplier wording, not yet normalized
Reported heat capture
Up to 98% per rack with the full stackSupplier wording, not yet normalized
Manufacturer
Supermicro

Connected records

Compatible architecture

Connected records

Equipment category

Evidence ledger

Sources and evidence

The links below show where the factual claims came from. Supplier specifications remain supplier-reported unless the record names independent operating evidence.

  1. 01
  2. 02
Record information
Record ID
DCC / PROD / SUPERMICRO-I
Record reviewed
Sept. 4, 2026
Newest source published
May 14, 2025
Record first published
Sept. 4, 2026
External sources
2
Search visibility
Offered to search engines

Required fields this record has not addressed yet, most important first:

  • Rating conditions
  • Total coolant flow
  • Facility-water supply and return
  • Public deployment evidence
  • Pressure or head
  • Fluid compatibility
  • Deployment format

Decide between

Comparable products

The same equipment category from other manufacturers, most-evidenced first.

View all products

Add two or more, then open the comparison to see every stated claim, its duty point, and its source side by side.

Direct answers

Frequently asked questions

Direct answers drawn from the record, its comparison fields, and the evidence linked below.

What is the Supermicro In-Rack CDU?

Supermicro's in-rack coolant distribution unit puts the heat exchanger inside the rack it serves, which shortens the loop and lowers the pressure the pumps must overcome. It occupies 4U and is rated to 250 kW, enough for one dense rack. Supermicro states operation on water up to 45 degrees Celsius, which removes the mechanical chiller from the critical path, and pairs that with a claim of up to 98 percent heat capture per rack when the whole DLC-2 stack is used. The remaining few percent still leaves through air, so the room cannot be treated as thermally neutral. Two variants are listed: an EIA model with 2N redundant pumps drawing up to 1.2 kW, and an OCP model with N+1 pumps drawing up to 3 kW. Dimensions are 480 by 810 by 177 mm and 480 by 858 by 177 mm respectively, at 100 and 114 kg dry. Power supplies are redundant. Management runs over Redfish, SNMP, a web interface and Supermicro's own orchestration software. An in-row unit at 1.8 MW is also offered for multi-rack pods. Supermicro does not publish the approach temperature, the flow rate, the secondary fluid, or the pressure drop, so the 250 kW figure cannot be compared directly with a rival quoted at a named approach.

Who makes the Supermicro In-Rack CDU?

Supermicro makes it. We file it under coolant distribution units, and its status is available.

What are the key specifications for the Supermicro In-Rack CDU?

Weight: 100 kg or 114 kg without coolant; Footprint: 480 × 810 mm or 480 × 858 mm, 4U high; Protocols: Redfish, SNMP, web interface. These figures come from the supplier. Before comparing two products, restate both at your own water temperatures, flow, pressure, and redundancy, because a rating measured under favorable conditions will not hold on site.