Public CDU specification dataset
Every coolant distribution unit in this database, with its published capacity, the duty point that capacity holds at, and whether a person has read the figure against its source.
- Rows
- 19
- Columns
- 13
- Version
- v4
- Generated
- 2026-11-08T10:46:14.837Z
- Identifier
- dcc:cdu-specifications
- Licence
- CC BY 4.0
19 rows. Public CDU specification dataset carries its methodology and limits inside the JSON file, so the file can be read without this page.
What you can answer with it
- Compare CDU capacity across suppliers without comparing a rated figure against a nominal one.
- See which suppliers publish a duty point at all, which is itself a procurement signal.
- Cite a capacity with its source rather than with a vendor deck.
How the rows were built
- Rows are generated from the product records on this site, not maintained separately. A correction to a record changes this dataset on the next build.
- A figure is taken from a reviewed claim when one exists, and from the supplier's published specification otherwise. The evidence column says which, in every row: “As published” means no editor has yet read that figure against its source.
- Values are shown as the supplier stated them alongside a canonical unit, so 2 MW and 2,000 kW are one figure rather than two.
- A blank is written as “Not stated”. No figure is inferred from a comparable product, a datasheet family, or a press release adjective.
The full editorial standard, including how sources are ranked and how project stages are labelled, is on the methodology page.
What it does not cover
- Coverage is what this database holds, which is not the whole market. Absence from this file is not evidence that a product does not exist.
- A duty point is only present where the supplier published one. Capacities without one cannot be compared with capacities that have one.
- The evidence column says who stated a figure, not that anyone witnessed a test. “Supplier reported” is the most common value in this market and is not a criticism.
- Prices, lead times, and availability are not here, because this site does not hold figures a supplier will not publish.
PreviewFirst 12 of 19 rows
| Supplier | Product | Lifecycle | Rated capacity | Duty point | Total coolant flow | Approach temperature | Secondary fluid | Footprint | Evidence | Sources | Reviewed | Record |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Carrier | Carrier CDU 65LL | Available | 1,350 kW at 4°C approach | No duty point stated | 0 to 1,650 liters per minute at 350 kPa, single pump | 4°C, or 2°C with the high-efficiency exchanger | Not stated | Not stated | As published | 2 | Sept. 4, 2026 | Open record |
| Chilldyne | Chilldyne CF-CDU300 | Available | 300 kW at 7°C approach | No duty point stated | Up to 300 liters per minute | 7°C at 300 kW, 2°C at 200 kW | Water or water-glycol | 24 × 80 × 45 in | As published | 2 | Sept. 4, 2026 | Open record |
| Daikin | Daikin Coolant Distribution Unit | Available | 400 kW, 1,000 kW or 2,000 kW | No duty point stated | Not stated | Down to 2 K | Not stated | Not stated | As published | 2 | Sept. 4, 2026 | Open record |
| Rittal | Rittal CDU In-Row | Available | 1,000 kW at 4 K approach; 1,500 kW at 6 K approach | No duty point stated | Up to 1,500 liters per minute | 4 K or 6 K as quoted | Not stated | 600 × 1,400 mm, 2,300 mm tall | As published | 2 | Sept. 4, 2026 | Open record |
| Supermicro | Supermicro In-Rack CDU | Available | Up to 250 kW | No duty point stated | Not stated | Not stated | Not stated | 480 × 810 mm or 480 × 858 mm, 4U high | As published | 2 | Sept. 4, 2026 | Open record |
| Accelsius | Accelsius NeuCool IR80 | Available | 80 kW | No duty point stated | Not stated | Not stated | Non-conductive dielectric | Not stated | Supplier reported | 2 | Aug. 9, 2026 | Open record |
| Boyd | Boyd ROL4000 | Available | 2 MW at 3°C approach | No duty point stated | 1,890 liters per minute (500 gallons per minute) | 3°C | Not stated | 1,651 × 1,199 × 2,364 mm | As published | 1 | Sept. 4, 2026 | Open record |
| DCX Liquid Cooling | DCX Enterprise ECDU 1380/2600 | Available | 1.38 MW to 2.6 MW | No duty point stated | Up to 3,333 liters per minute, single pump | Not stated | Not stated | 600 mm or 800 mm wide, standard rack depth | As published | 1 | Sept. 4, 2026 | Open record |
| Delta Electronics | Delta GoCool-1000 | Available | 1,000 kW at 5°C approach; 750 kW at 4°C approach | No duty point stated | 1,000 liters per minute secondary; 1,200 primary | 5°C at rated capacity | 25% propylene glycol | 900 × 1,360 mm, 2,300 mm tall | As published | 1 | Sept. 4, 2026 | Open record |
| Kelvion | Kelvion Centralised Coolant Distribution Unit | Available | Skids above 9 MW and above 4 MW as delivered | No duty point stated | Not stated | Not stated | Not stated | Not stated | As published | 1 | Sept. 4, 2026 | Open record |
| LITE-ON | LITE-ON CL-LL-WCDU-6011 | Available | 600 kW at 600 liters per minute, 4°C approach | No duty point stated | 600 liters per minute at 2.45 bar external differential | 4°C | Treated water or 25% propylene glycol | 900 × 1,200 mm, 2,038 mm tall | As published | 1 | Sept. 4, 2026 | Open record |
| nVent | nVent RackChiller CDU800 | Available | More than 800 kW at 6 K approach | No duty point stated | 850 liters per minute, primary | 6 K | Not stated | 800 × 1,200 mm, 2,200 mm tall | As published | 1 | Sept. 4, 2026 | Open record |
Data dictionary13 columns
supplierSupplier- The manufacturer named on the product record.
productProduct- The supplier's own model name, not a normalized family.
statusLifecycle- Availability as the supplier states it: shipping, announced, or withdrawn.
capacityRated capacity- Headline thermal capacity, shown as published with a canonical unit beside it.
dutyPointDuty point- The conditions the capacity holds at. “No duty point stated” means the supplier published none.
flowTotal coolant flow- Secondary-loop flow as published. Flow per kilowatt is a separate claim and is not mixed in here.
approachApproach temperature- Difference between facility-water supply and technology-water supply at the rated point.
fluidSecondary fluid- Coolant the technology loop is rated for.
footprintFootprint- Physical dimensions or rack units as published.
evidenceLevelEvidence- Who stands behind the capacity figure. “As published” means no editor has read it against its source yet.
sourcesSources- Count of cited sources on the underlying record.
reviewedReviewed- When a human last read the record this row came from.
recordRecord- Canonical URL of the record, so every row is traceable.
Versions and change log
This file is v4, generated 2026-11-08T10:46:14.837Z from 19 records. The version counts the publishes that changed this file, so it never moves backwards and a citation keeps meaning what it meant. The rows themselves are always regenerated from the records, so a correction reaches the file as soon as it reaches the record.
- v4Published by event research-correction-2026-10-04-1791102709240.
- v3Published by event research-correction-2026-10-04-1791102066737.
- v2Published by event research-correction-2026-10-04-1791101342042.
- v1Published by event research-release-plant-cooling-2026-rack-loop-2026-fluids-controls-2026.
No published change has touched a record in this file yet. When one does, it appears here rather than only in the file.
Formats and licence
- CSVAvailable at /datasets/cdu-specifications/data.csv, RFC 4180 quoted.
- JSONAvailable at /datasets/cdu-specifications/data.json, with the same columns and row order.
- ParquetNot published. The row counts here do not justify it yet, and offering a format we do not regenerate would be worse than not offering it.
- APINo query API. The JSON file is the whole dataset, so fetching it is the API for now.
Licensed CC BY 4.0: Free to use, republish, and build on, including commercially, with attribution to DataCenterChill and a link to the dataset page. Read the licence.
Citing and correcting
Cite it as: DataCenterChill, Public CDU specification dataset (dcc:cdu-specifications), v4, https://www.datacenterchill.com/datasets/cdu-specifications. Quoting a figure without the conditions in its row is the error this file exists to prevent, so keep them together.
A row that is wrong is a record that is wrong. Send the source and the correction reaches the record, this file, and every page connected to it.